Exergetic Comparison of Single and Double Effect Absorption Cooling Cycles
Küçük Resim Yok
Tarih
2017
Yazarlar
Dergi Başlığı
Dergi ISSN
Cilt Başlığı
Yayıncı
Erişim Hakkı
info:eu-repo/semantics/openAccess
Özet
Absorption cooling cycles are environmental and can use solar or waste heat for cooling with very small electric power. This workpresents exergy analysis of a double effect parallel flow and single effect absorption cooling systems for comparison. A computerprogram is developed for the thermodynamic properties of lithium bromide-water solutions by the author in FORTRAN codes forthe exergy analysis. The double effect parallel flow absorption systems have better advantages than the single effect absorption system.The coefficient performance (COP) and the exergetic coefficient performance (ECOP) of the double effect parallel flow absorptionsystems are higher than the single cycles. For the double effect cycle COP and ECOP are found as 1.195 and 0.28, and for the singleeffect cycle COP and ECOP are found as 0.68 and 0.23, respectively. For each component the exergy loss and exergy destruction iscalculated. Most of the irreversibilities are found in the evaporator and in the absorber which about 74 % for the double effect, and 72% for the single effect of the total irreversibility. It is concluded that the performance of the evaporator and the absorber is crucial forthe two cycles. Improving and better design of these two components will directly improve and affect positively the working conditionsand the performance of the cycles.