ANALYSIS OF HEAT PUMPS WITH ZEOTROPIC REFRIGERANT MIXTURES BY TAGUCHI METHOD
Küçük Resim Yok
Tarih
2010
Dergi Başlığı
Dergi ISSN
Cilt Başlığı
Yayıncı
Turkish Soc Thermal Sciences Technology
Erişim Hakkı
info:eu-repo/semantics/closedAccess
Özet
The goal of this work is to determine the optimum set of parameters by using the Taguchi method in vapour compression heat pump systems. The experimental apparatus consist of an air-to-liquid vapor compression heat pump, a water cooled condenser, a forced air evaporator, an electrical air and water heaters, and various measuring elements and other auxiliary equipments. Refrigerants R22, R407C, and five of their binary mixtures which contain about 0%, 25%, 50%, 75%, and 100% mass fractions of R407C were tested. To determine the effect of the chosen parameters on the system and optimum working conditions, an experimental design method suggested by Genichi Taguchi was used. The most effective parameters are found to be the condenser water mass flow rate for the coefficient of performance and to be condenser water inlet temperature for the exergetic efficiency.
Açıklama
Anahtar Kelimeler
Heat pump, R22, R407C Zeotropic mixture, Taguchi method, Optimum working conditions
Kaynak
Isi Bilimi ve Teknigi Dergisi-Journal of Thermal Science and Technology
WoS Q Değeri
Q4
Scopus Q Değeri
Cilt
30
Sayı
2